Chapter 11 Summary of Parameter SettingsME300
11-38
Pr.
Explanation Settings Default
12-14
Selection of pump start-up
sequence
0: By pump’s ID #
1: By the running time.
1
12-15
Running time of
multi-pump under
alternative operation
0.0–360.0 sec. 60.0
12-16
Assign the setting for
Pr.08-13 PID feedback
level
0: Use the current setting (default), verify if any error by
checking feedback deviation.
1: Set low water pressure percentage (%), verify if any
error by checking physical quantity value’s feedback.
0
12-20
Simple positioning stop
frequency 0
0.00–599.00 Hz 0.00
12-21
Simple positioning stop
frequency 1
0.00–599.00 Hz 5.00
12-22
Simple positioning stop
Frequency 2
0.00–599.00 Hz 10.00
12-23
Simple positioning stop
frequency 3
0.00–599.00 Hz 20.00
12-24
Simple positioning stop
frequency 4
0.00–599.00 Hz 30.00
12-25
Simple positioning stop
frequency 5
0.00–599.00 Hz 40.00
12-26
Simple positioning stop
frequency 6
0.00–599.00 Hz 50.00
12-27
Simple positioning stop
frequency 7
0.00–599.00 Hz 60.00
12-28
Delay time of simple
positioning stop 0
0.00–600.00 sec. 0.00
12-29
Delay time of simple
positioning stop 1
0.00–600.00 sec. 0.00
12-30
Delay time of simple
positioning stop 2
0.00–600.00 sec. 0.00
12-31
Delay time of simple
positioning stop 3
0.00–600.00 sec. 0.00
12-32
Delay time of simple
Positioning Stop 4
0.00–600.00 sec. 0.00
12-33
Delay time of simple
positioning stop 5
0.00–600.00 sec. 0.00
12-34
Delay time of simple
positioning stop 6
0.00–600.00 sec. 0.00