THERMISTOR ADJUSTER
Do an ohms resistance check across the terminals. Proper ohms reading is approximately 23,200 ohms
± 10%.
P2
THERMISTOR
ADJUSTER
TO THERMISTOR
NOTE: Dometic refrigerators do not come equipped with a
thermistor adjuster. This is an add-on component.
THERMISTOR
ADJUSTER
TO THER-
MISTOR
SOLENOID VALVE
Check the solenoid with a properly calibrated ohm meter. Remove the connector from the solenoid and
measure the resistance across the terminals. The proper reading would be 49 ohms with tolerance
range of ten percent.
Next, hook up a manometer at the test port. Then check for DC volts at gas valve terminals while the
unit is in trial-for-ignition. If DC volts are present and pressure is low, replace the valve. If DC volts are
not present at the valve while the unit is in trial-for ignition, verify that the wire at Plug 3, Terminal 2 on
lower circuit board has DC volts (9 or more).
AMES/AES
REFRIGERATORS
ROYALE AND ELITE
REFRIGERATORS
P1
P2
P3
J1 J2 J3 J4 J5 J6 J7 J8 J10
35 A MP
FUSE
3 A MP F USE
FIVE
AMP
FUSE
3
2
1
6
5
4
3
4
1
2
Manual Compliments of
Northwest RV Supply
Printed From
http://www.nwrvsupply.com

Other manuals for Dometic RM3862

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Dometic RM3862 and is the answer not in the manual?

Dometic RM3862 Specifications

General IconGeneral
BrandDometic
ModelRM3862
CategoryRefrigerator
LanguageEnglish

Related product manuals