PowerSeries Neo Installation Guide
SIA False Alarm Reduction Installations: Quick Reference
Minimum required system consists of one Control unit model HS2128 or HS2064 or HS2032 or HS2016 and any one of the compatible listed keypads:
HS2LCDRF9, HS2LCDRFP9, HS2ICNRF9, HS2ICNRFP9, HS2LCD, HS2LCDP, HS2ICN, HS2ICNP, HS2LED HS2TCHP.
The following wireless keys can also be used in SIA compatible installations: PG9929, PG9939,PG9949.
Note: For models PG9929 and PG9939, the panic/emergency key shall be disabled for SIA compliant installations.
For a list of the default values programmed when the unit is shipped from the factory, and for other programming information, refer to the following
table.
The following optional subassembly modules also bear the SIA CP-01-2010 classification and may be used if desired: HSM2108 zone expander,
HSM2208 PGM output module, HSM2300 auxiliary power supply, HSM2204 output module, HSM2HOST9 2-way wireless transceiver, PG9901
indoor siren, PG9911 outdoor siren, and 3G2080(R)/ TL2803G(R)/ TL280(R) cellular and PSDN communication module.
Caution
l For SIA FAR installations use only modules/devices that are listed on this page.
l Fire Alarm Verification feature (Auto Verified Fire Zone type [025]) is not supported on 2-wire smoke detectors zones, model FSA-210B(T)
(S)(ST)(LST)(R)(RT)(RD)(RST)(LRST). This feature may be enabled for 4-wire smoke detectors only (FSA-410B(T)(S)(ST)(LST)(R)(RT)
(RST)(LRST) and wireless detectors PG9916/PG9926). The fire alarm delay is 60s.
l Call Waiting Cancel (Section [382], option 4) on a non-Call Waiting line will prevent successful communication to the supervising station.
l All system smoke detectors must be tested annually by conducting an Installer Walk Test. Prior to exiting Walk Test mode, a sensor reset must
be done on the system, [*][7][2], to reset all latching 4-wire smoke detectors. Refer to the installation instructions supplied with the detector for
details.
Notes
l Programming at installation may be subordinate to other UL requirements for the intended application.
l Cross zones have the ability to individually protect the intended area (e.g. motion detectors which overlap).
l Cross zoning is not recommended for line security Installations nor is it to be implemented on exit/entry zones.
l This control panel has a communication delay of 30 seconds. It can be removed or increased up to 45 seconds by the end user with installer con-
sultation.
l The system shall be installed with the sounding device activated and the communicator enabled for transmission using SIA or CID format.
l ULC commercial burglary installations require DEOL resistors.
- 23 -