Section 8: Programming Descriptions
The following is a brief description of the features and options available in the control panel.
Section [000] Keypad Function Key Programming
The five function keys can be reprogrammed with following functions. See Keypad Function Key Programming on page 15 for defaults.
Section [001]-[002] Zone Definitions
Option Description Option Description
[00] Null Key: Program non functioning keys with this option [14] Command Output #2: See [][7][1] on page 12
[03] Stay Arm: See Stay Arm on page 10 [16] Quick Exit: See [][0] on page 12
[04] Away Arm: See Away Arm on page 10 [17] Reactivate Stay/Away Zones: See [][1] on page 10
[05] No Entry Arm: See [][9] on page 12 *[27] Disarm: See Disarm on page 10
[06] Chime On/Off: See [][4] on page 11 *[29] [A]ux Alarm: Same as [A] key
[08] Bypass: See [][1] on page 10 *[30] [P]anic: Same as [P] key.
[13] Command Output #1: See [][7][1] on page 12 *Applies to Key Fobs only (See Section [804] Subsection [61]-[76])
Option Description
[00] Null Zone: Zone not used.
[01] Delay 1: When armed, provides entry delay when violated (follows Entry Delay 1).
[02] Delay 2: When armed, provides entry delay when violated (follows Entry Delay 2).
[03] Instant: When armed, instant alarm when violated.
[04] Interior: When armed, instant alarm if the zone is violated first, will follow entry delay if entry delay is active.
[05] Interior Stay/Away: Similar to ‘Interior’ except panel will auto-bypass the zone if armed in the Stay mode.
[06] Delay Stay/Away: Similar to ‘Delay 1’ except panel will auto-bypass the zone if armed in the Stay mode.
[07]-[08] Future Use
[09] 24-Hour Supervisory (Hardwired): Instant Alarm, silent at default.
[10] 24-Hour Supervisory Buzzer: Instant alarm, panel will activate keypad buzzer instead of bell output.
[11] 24-Hour Burglary: Instant alarm when violated, audible alarm at default.
[12] Future Use
[13] 24-Hour Gas: Instant alarm when violated, audible alarm at default.
[14] 24-Hour Heat: Instant alarm when violated, audible alarm at default (also known as high-temp).
[15] 24-Hour Medical: Instant alarm when violated, audible alarm at default.
[16] 24-Hour Panic: Instant alarm when violated, audible alarm at default.
[17] 24-Hour Emergency: Instant alarm when violated, audible alarm at default.
[18] Future Use
[19] 24-Hour Water: Instant alarm when violated, audible alarm at default (also known as flood).
[20] 24-Hour Freeze: Instant alarm
when violated, audible alarm at default (also known as low-temp).
[21] Future Use
[22] Momentary Keyswitch Arm: Arms or disarms the system when violated.
[23] Maintained Keyswitch Arm: Arms system when violated, disarms system when restored.
[24] For Future Use
[25] Interior/Delay: Function as an Interior zone when armed in Away mode, and as a Delay zone when armed in the Stay mode.
[26] 24-Hour Non-Alarm: Zone will NOT create an alarm. Can be used with chime to identify a specific event.
[27]-[31] Future Use
[32] Instant Stay/Away: Similar to ‘Instant’ except panel will auto-bypass the zone if armed in the Stay mode.
[33]-[35] Future Use
[36] 24-Hour Non-Latching Tamper: Instant tamper condition when violated. Active in armed and disarmed state.