8.4 Environmental and safety
Standards
IEC/EN 62040-1 Safety
IEC/EN 62040-2 Electromagnetic Compatibility EMC
IEC/EN 62040-3 Performance
EMC (Emissions)
CISPR32 Class A
IEC/EN 61000-3-2 Flickers
IEC/EN 61000-3-3 Harmonics
This is a category C2 (Class A) UPS product. In a residential environment,
this product may cause radio interference, in which case the user may be
required to take addition measures.
EMC (Immunity)
IEC 61000-4-2, (ESD): 4 kV Contact Discharge / 8 kV Air Discharge
IEC 61000-4-3, (Radiated field): 10 V/m
IEC 61000-4-4, (EFT): 4 kV
IEC 61000-4-5, (Surges): 1 kV Differentiel Mode / 2 kV Common Mode
IEC 61000-4-6, (Electromagnetic field): 10 V
IEC 61000-4-8, (Conducted magnetic field): 30 A/m
Agency markings
CE, EAC, Cm, Ukr, UKCA,
Protection degree IP20
Earthing system
This UPS can be connected to TN, TT, IT electrical supply system, same
system is supplied to the load.
Protective Class
Class I
Operating temperature 0 to 40 °C (32 to 104 °F)
Storage temperature
0 to 40 °C (32 to 104 °F) with battery
-25 to 55 °C (-13 to 131 °F) without battery
Relative humidity
Storage: 0-93 % non-condensing
Operation: 0-85 % non-condensing
Operating altitude
2000 m
Transit altitude Up to 10,000 meters (32,808 ft) above sea level
Audible noise
550VA/700VA/900VA/1200VA: <25dBA
1600VA/2200VA: <25dBA (Line Mode), <40dBA (battery or AVR mode)