2.2 Standards:
The units with CE and KC markings comply with the following standards:
* Safety
IEC/EN 62040-1-1
*EMS
ESD........................................................:IEC/EN 61000-4-2 Level 4
RS..........................................................:IEC/EN 61000-4-3 Level 3
EFT.........................................................:IEC/EN 61000-4-4 Level 4
SURGE..................................................:IEC/EN 61000-4-5 Level 4
CS..........................................................:IEC/EN 61000-4-6 Level 3
PFMF.......................................................IEC/EN 61000-4-8 Level 4
Low Frequency Signals.........................:IEC/EN 61000-2-2
* EMI -For 1000H(XL) / 2000H(XL) / 3000H(XL)
Conducted Emission...............................:IEC/EN 62040-2 C2
Radiated Emission..................................:IEC/EN 62040-2 C2
Harmonic Current....................................:IEC/EN 61000-3-2
Voltage Fluctuation and Flicker...............:IEC/EN 61000-3-3
Warning: This is a category C2 UPS product. In a residential invironment, this
product may cause radio interference, in which case the user may be required
to take additional measures.
* EMI -For 6000H(XL) / 10000H(XL)
Conducted Emission.................................:IEC/EN 62040-2 C3
Radiated Emission....................................:IEC/EN 62040-2 C3
Warning: This is a product for commercial and industrial application in the
second environment installation restrictions or additional measures may be
needed to prevent disturbances.