WALL-MOUNTED BYPASS SWITCH INSTALLATION
Eaton 9155 UPS (8–15 kVA) User's Guide S 164201553 Rev G (www.eaton.com/powerquality)
38
ON
OFF
UPS Wiring
Access Cover
Conduit Landing
Battery Circuit Breaker
Figure 25. UPS Rear View
7. Install the conduit to the bypass switch cabinet. AC input and AC output
conductors must be run through separate conduit. UPS output circuits must be
installed in a dedicated conduit system and not shared with other electrical
circuits.
8. Hardwire the terminal strip inside the bypass switch cabinet. Use copper wire
that is the appropriate size for the current draw.
See Figure 26 for a detailed view of the terminal strip label.
Figure 26. Wall-Mounted Bypass Switch Terminal Strip Wiring