2.6 Connections with a FlexPDU (Power Distribution Unit) module (optional)
7
45 46 48
8 9
1. Connect the UPS socket (9) to the AC-power
source using the power cable from the equip-
ments to be protected.
2. Connect the input socket on the FlexPDU
module (48) to the UPS outlet (7) or (8). The
cable and the connectors are marked in red.
3. Connect the equipment to the outlets (45)
and (46) on the FlexPDU module. These
outlets differ, depending on the version of the
FlexPDU module.
2.7 UPS Connection
i
Check that the indications on the rear panel of the silkscreen of the UPS correspond to the AC-power source and the
true electrical source of the required load.
Tower model
1. Connect the input plug (9) to the AC power
source using the power cable from the equip-
ments to be protected.
2. Connect the loads to the UPS.
It is preferable to connect the priority loads to the
outlets marked (8) and the non-priority loads to
the outlets marked (7) that can be programmed in
pairs (1 and 2). To program the outlets, the EATON
communications software is required.
RT model
i
Note. The UPS charges the battery as soon as it is connected to the AC-power source, even if button (27) is not pressed.
Once the UPS is connected to the AC-power source, eight hours of charging are required before the battery can supply
the rated backup time.
86-86700-00EN A02 - Page 15
2. Installation

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Eaton EX 700 and is the answer not in the manual?

Eaton EX 700 Specifications

General IconGeneral
Noise level45 dB
Output power630 W
Input frequency40/70 Hz
Output power capacity0.7 kVA
Input operation voltage (max)284 V
Input operation voltage (min)100 V
Output operation voltage (max)250 V
Output operation voltage (min)200 V
Power plugC14 coupler
AC outlet typesC13 coupler
AC outlets quantity6 AC outlet(s)
USB 2.0 ports quantity1
SafetyIEC/EN 62 040-1, IEC/EN 62 040-2, IEC/EN 62 040-3 (VFI-SS-113), IEC/EN 60 950-1 (RD)
Form factorTower
Product colorGray
LED indicatorsYes
Typical backup time at full load- min
Typical backup time at half load16 min
Operating temperature (T-T)0 - 40 °C
Weight and Dimensions IconWeight and Dimensions
Depth440 mm
Width153 mm
Height242 mm
Weight12500 g