5.2 Battery-Module Replacement
Safety recommendations
The battery can cause electrocution and high short-circuit currents. The following safety cautions are required
before servicing the battery components:
w Remove watches, rings, bracelets and all other metal objects from the hands and arms.
w Use tools with an insulated handle.
Battery-module removal
D Remove the metal protection cover in front of the
battery (two screws).
E Turn the connector.
F Pass the connector through the hole.
RT model
B
A
C
A Unscrew the left-hand side of the front panel (two
screws).
B Remove the part.
C Disconnect the battery block by separating the
two connectors (never pull on the wires).
F
E
D
86-86700-00EN A02 - Page 24
5. Maintenance

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Eaton EX 700 and is the answer not in the manual?

Eaton EX 700 Specifications

General IconGeneral
Noise level45 dB
Output power630 W
Input frequency40/70 Hz
Output power capacity0.7 kVA
Input operation voltage (max)284 V
Input operation voltage (min)100 V
Output operation voltage (max)250 V
Output operation voltage (min)200 V
Power plugC14 coupler
AC outlet typesC13 coupler
AC outlets quantity6 AC outlet(s)
USB 2.0 ports quantity1
SafetyIEC/EN 62 040-1, IEC/EN 62 040-2, IEC/EN 62 040-3 (VFI-SS-113), IEC/EN 60 950-1 (RD)
Form factorTower
Product colorGray
LED indicatorsYes
Typical backup time at full load- min
Typical backup time at half load16 min
Operating temperature (T-T)0 - 40 °C
Weight and Dimensions IconWeight and Dimensions
Depth440 mm
Width153 mm
Height242 mm
Weight12500 g