EasyManuals Logo
Home>Eaton>UPS>Pulsar Series

Eaton Pulsar Series User Manual

Eaton Pulsar Series
104 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #27 background imageLoading...
Page #27 background image
6. Appendices
6.1 Technical Specifications
Evolution S
1250
Evolution S
1750
Evolution
2000
Evolution S
2500
Evolution S
3000
Output power
1250VA/1150W 1750VA/1600W 2000VA/1600W 2500VA/2250W 2880VA/2700 W
AC input power
w Rated input voltage
w Input-voltage range
w Input-frequency range
Single phase 120 V
89 V to 151 V
(1)
47 Hz to 70 Hz, 56.5 Hz to 70 Hz (60 Hz system)
(2)
Output on battery power
w Voltage
w Frequency
120 V (+6/-10%)
(3)
50/60 Hz ±0.1%
Battery (sealed lead acid,
maintenance free)
w Standard
w Additional modules possible
(up to 4 EXB)
4 x 12 V
7.2 Ah
4 x 12 V 9 Ah
6 x 12 V
7.2 Ah
6 x 12 V
9 Ah
Evolution S EXB 1250/1750
(4)
No Evolution EXB S 2500/3000
(5)
Environment
w Operating temperature range
w Storage temperature range
w Relative humidity
w Noise level
0 to 40ºC
-20ºC to 50ºC
20 to 90% (without condensation)
< 45 dBA < 50 dBA
(1) The high and low thresholds can be adjusted using Personal Solution-Pac software.
(2) Up to 40 Hz in low-sensitivity mode (programmable using Personal Solution-Pac software.
(3) Adjustable to 100 V (10% derating of output power) 120 V / 127 V.
(4) Battery Evolution S EXB 1250/1750: 2 strings, each 4 x 12 V / 9 Ah.
(5) Battery Evolution S EXB 2500/3000: 2 strings, each 6 x 12 V / 9 Ah.
This product is designed for IT power distribution system.
86-81710-00EN A03 - Page 25

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Eaton Pulsar Series and is the answer not in the manual?

Eaton Pulsar Series Specifications

General IconGeneral
BrandEaton
ModelPulsar Series
CategoryUPS
LanguageEnglish

Related product manuals