EasyManuals Logo
Home>elco>Burner>Firebird FB 2 K LN

elco Firebird FB 2 K LN User Manual

elco Firebird FB 2 K LN
64 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #30 background imageLoading...
Page #30 background image
INSTALLATION
30/64
EN
4.8 Electrical connection
DANGER
Danger of death caused by live components!
Contact with live parts can lead to serious injury, take the following precautions:
- ensure that the power is switched off for all electrical parts
- electrical wiring installation must be carried out by qualied personnel and in compliance with
the regulations currently in force in the country of destination. Refer to the wiring diagrams.
CAUTION
- The electrical installation should include a minimum of a type A MCB.
- Check to ensure that the power supply voltage is as specied in the electric diagram and in
data plate.
- Burner fuse: 3 Amps.
WARNING
- Use exible cables in compliance with the EN 60 335-1 standard. Assure a correct earth
connection.
- The wiring section must be minimum 1 mm
2
(in any case verify with the standard and local
rules).
- This control ame is equipped with the post ventilation function. Other versions of the burner
are not to be tted.
- Check operation of boiler thermostatic control.
- Check operation of Photocell by withdrawing from burner and then covering to simulate ame
out condition.
CAUTION
WARNING

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the elco Firebird FB 2 K LN and is the answer not in the manual?

elco Firebird FB 2 K LN Specifications

General IconGeneral
Brandelco
ModelFirebird FB 2 K LN
CategoryBurner
LanguageEnglish

Related product manuals