25
Installation
Cascade accessories
The pipe work headers are available
in 2 dimensions, i.e. DN65 and DN100
and are connected to one another
bytheangecouplingsandgaskets,
M12 or M16x55 bolts, spring washers
and nuts. The low loss header and
the complete installation can then be
connected to it.
1.2.3. Low loss header
There are 4 low loss headers available:
- Low loss header for 1 THISION
L PLUS to max. 200kW supplied
with automatic air vent, drain valve
and pocket for temperature sensor
T10. Boiler connections are 2x 2",
installation connections are 2x 2".
The low loss header MUST be
connected between the boiler[s] and
the system pumps.
- Low loss headers DN65 to 452kW
- Low loss headers DN100 to 1000kW
- Low loss header DN100 DUO to
1600kW.
The low loss headers comes standard
with adjustable feet, automatic air vent,
drain valve, pocket for temperature
sensor T10, M12 or M16x55 bolts,
spring washers and nuts.
The low loss header can be positioned
on either the left or right hand side of
the pipe work headers.
4. Flow temperature sensor T10
Every system with 1 or more THISION
L PLUS-boilers must be provided with
aowtemperaturesensorT10and
must be connected on the master
boiler(MTS1-T10).Theowsensor
must be placed in the pocket of the low
loss header.
5. Set of bends
The low loss header can be positioned
at a 90° angle. A set of bends may be
used for that purpose.
-BendssetDN65ow/return
-BendssetDN100ow/return
6. Blanking anges
The ends of the pipe work headers
havetobettedwithblankinganges.
Theblankingangescomestandard
withafullycongureddelivery,
including bolts, spring washers and
gaskets.
-BlankingangesetDN65ow/return
2 items
-BlankingangesetDN100ow/return
2 items
7. Welded-on anges
Uponrequest,welded-onangesare
available to connect CH-pipe lines
to the secondary side of the low loss
header and to connect the gas line.
-Welded-onangesetDN65ow/
return 2 items + DN65 gas 1 item
-Welded-onangesetDN100ow/
return 2 items + DN65 gas 1 item
For complete overview on
available accessories please refer
to paragraph “THISION L PLUS
Cascade accessories “.
Required components that are not
supplied by ELCO:
- The installation pump;
- The condensate discharge system
-Theinstallationwaterlter;
- Air and dirt separator;
- Hot water supply;
- Regulation valve;
- Expansion vessel(s).
6
7
1
2
3
4
5

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the elco THISION L PLUS and is the answer not in the manual?

elco THISION L PLUS Specifications

General IconGeneral
Brandelco
ModelTHISION L PLUS
CategoryBoiler
LanguageEnglish

Related product manuals