32
Application Engineering
BULLETIN
AE4-1383 R5
© 2012 Emerson Climate Technologies, Inc.
Printed in the U.S.A.
Table 7
CoreSense
Diagnostics Fault Codes
Fault Code Code Description
Protection
Shutdown
(Default)
Protection
Off Time
(Default)
Consecutive
Detections
Until Lockout
Lockout Feature is NOT enabled from the factory except on code 7
1
High Discharge Temp
See Diagram For Setting
Yes 20 Min. 4
2
Excess System Limit Trips -
4 Consecutive System Limit Trips Having 1-15
Min Runtime Each
Yes 5 Min. No Lockout
3
Excessive Demand Cycling -
Default is 240 Cycles Per 24 Hr Period
No - -
4
Locked Rotor -
Compressor Did Not Start Within Alloted Time
Yes 20 Min. 4
5
Demand Present -
No Current Detected Over 4 Hr Period
No - -
6
Phase Loss Detected Yes 20 Min. 10
7
Reversed Phase Detected Yes
Until Module
Is Reset
1
8
Welded Contactor -
Current Detected Without Demand
No
1
--
9
Low Module Voltage Yes 5 Min. No Lockout
10
Module Communications Error No - -
11
Discharge Temperature Sensor Error No - -
12
Current Transducer Error No - -
Lockouts Can Be Enabled By Dip Switch 6 Setting
1
Code 8 Displays For 24 Hr After Last Detection
The M1-M2 relay only opens during a protection shutdown. To reset module, cycle module power.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emerson Copeland Scroll K5 Series and is the answer not in the manual?

Emerson Copeland Scroll K5 Series Specifications

General IconGeneral
BrandEmerson
ModelCopeland Scroll K5 Series
CategoryAir Compressor
LanguageEnglish

Related product manuals