EasyManuals Logo
Home>Emerson>Controller>Fisher FIELDVUE DVC6000 HW2

Emerson Fisher FIELDVUE DVC6000 HW2 User Manual

Emerson Fisher FIELDVUE DVC6000 HW2
120 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #19 background imageLoading...
Page #19 background image
Instruction Manual
D103785X012
Configuration
June 2017
19
Section 3 Configuration
Guided Setup
Field Communicator Configure > Guided Setup (2‐1)
The following procedures will guide you through the instrument setup process.
DDevice SetupThis procedure is used to configure actuator and valve information, calibrate the valve assembly, and
assign the tuning set for the valve assembly.
DPerformance Tuner (instrument level AD, PD, ODV)This procedure executes a simple step response test and then
calculates a recommended set of gain values based on the response of the control valve. See page 30 for additional
information.
DStabilize Optimize (instrument level HC)—This procedure permits you to adjust valve response by changing the
digital valve controller tuning. See page 30 for additional information.
Manual Setup33
Manual Setup allows you to configure the digital valve controller to your application. Table 3‐1 lists the default settings
for a standard factory configuration. You can adjust actuator response, set the various modes, alerts, ranges, travel
cutoffs and limits. You can also restart the instrument and set the protection.
Table 3‐1. Default Detailed Setup Parameters
Setup Parameter Default Setting
(1)
Instrument
Configuration
Control Mode Analog
Restart Control Mode Resume Last
Analog In Range Low 4 mA
Analog In Range High 20 mA
Analog Input Units mA
Local AutoCal Button Disabled
Polling Address 0
Burst Mode Enable No
Burst Command 3
Cmd 3 (Trending) Pressure A-B
Dynamic Response and
Tuning
Input Characterization Linear
Travel Limit High 125%
Travel Limit Low -25%
Travel/Pressure Cutoff High 99.46%
Travel/Pressure Cutoff Low 0.50%
Set Point Rate Open 0%/sec
Set Point Rate Close 0%/sec
Set Point Filter Time (Lag Time) 0 sec
Integrator Enable Yes
Integral Gain 9.4 repeats/minute
Integral Deadzone 0.26%
-continued on next page-

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emerson Fisher FIELDVUE DVC6000 HW2 and is the answer not in the manual?

Emerson Fisher FIELDVUE DVC6000 HW2 Specifications

General IconGeneral
BrandEmerson
ModelFisher FIELDVUE DVC6000 HW2
CategoryController
LanguageEnglish

Related product manuals