Instruction Manual
D103785X012
Maintenance and Troubleshooting
June 2017
74
Disassembly
Note
If the feedback arm (key 79) or feedback arm assembly (key 84) is removed from the digital valve controller, the travel sensor
assembly [i.e. potentiometer/bushing assembly (key 223)] must be recalibrated.
DVC6015 Remote Feedback Unit
Refer to figure 7‐4 for key number locations.
1. Remove piping and fittings from the instrument.
2. Disconnect the adjustment arm from the connector arm and the feedback arm, see figure 6‐7.
3. Remove the instrument from the actuator.
4. Loosen the screw (key 80) that secures the feedback arm (key 79) to the travel sensor shaft.
5. Remove the feedback arm (key 79) from the travel sensor shaft.
6. Disconnect the three travel sensor assembly wires from the terminals.
7. Remove the screw (key 72) that fastens the travel sensor assembly to the housing.
8. Pull the travel sensor assembly (key 223) straight out of the housing.
Figure 6‐7. FIELDVUE DVC6015 Adjustment Arm
ADJUSTMENT ARM
CONNECTOR ARM
FEEDBACK ARM (KEY 79)
X0910

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emerson Fisher FIELDVUE DVC6000 HW2 and is the answer not in the manual?

Emerson Fisher FIELDVUE DVC6000 HW2 Specifications

General IconGeneral
BrandEmerson
ModelFisher FIELDVUE DVC6000 HW2
CategoryController
LanguageEnglish

Related product manuals