Quick Start Guide
D103556X012
DVC6200 Digital Valve Controllers
August 2015
35
Special Instructions for Safety Instrumented Systems
DVC6200 SIS instruments are identified by an SIS label on the terminal box cover. Refer to the Safety manual for
further information regarding the design, installation, and operation of the DVC6200 SIS product.
The following section illustrates typical installation scenarios for a DVC6200 SIS. The digital valve controller can be
configured to trip on low current (deenergize to trip, DETT) or high current (energize to trip, ETT). See figure 28 for
the DIP switch configuration of this action on the printed wiring board. This setting is preconfigured at the factory
when ordered properly.
Figure 28. DIP Switch Location
BACK OF PWB
ASSEMBLY SUB‐MODULE
PT-PT/
MULTI-DROP
SELECTION
DE-ENERGIZE TO TRIP
ENERGIZE TO TRIP
SELECTION
X0436
Table 2. DIP Switch Configuration
(1)
Switch Label Operational Mode DIP Switch Position
PT-PT 420 mA PointtoPoint Loop LEFT
Multi 24 VDC MultiDrop Loop RIGHT
Hardware Shutdown Enabled LEFT
Hardware Shutdown Disabled RIGHT
Trip Current Low (DETT) De-energize to trip LEFT
Trip Current High (ETT) Energize to trip RIGHT
1. Refer to figure 28 for switch location.
Note
DVC6200 SIS instruments in PTPT mode require the Hardware Shutdown Switch be Enabled for FMEDA failure rates to be valid for
4-20 mA operation.
WARNING
When Hardware Shutdown is enabled, the instrument will respond to a signal change regardless of instrument mode. The
valve may move in an unexpected direction when power is applied to the digital valve controller. To avoid personal injury
and property damage caused by moving parts, keep hands, tools, and other objects away from the valve/actuator assembly
when applying power to the instrument.
SIS

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emerson Fisher FIELDVUE DVC6200 HW1 and is the answer not in the manual?

Emerson Fisher FIELDVUE DVC6200 HW1 Specifications

General IconGeneral
BrandEmerson
ModelFisher FIELDVUE DVC6200 HW1
CategoryController
LanguageEnglish

Related product manuals