Quick Start Guide
D103556X012
DVC6200 Digital Valve Controllers
July 2017
10
Air‐to‐Open (667 size 30i - 76i and GX)
Vertically align the magnet assembly so that the center line of the alignment template is lined up as close as possible
with the upper
extreme of the valid travel range on the magnet assembly. The magnet assembly should be positioned
so that the index mark in the feedback slot of the DVC6200 housing is within the valid range on the magnet assembly
throughout the range of travel. See figure 7.
Figure 7. Air‐to‐Open Magnet Assembly Alignment
ALIGNMENT
TEMPLATE
INDEX MARK
FEEDBACK
PIECES
VALVE STEM
CONNECTOR
RETAINING
SLOT
NOTE:
1 IMAGE DENOTES ACTUATOR AT HALF TRAVEL. ALIGN UPPER EXTREME OF MAGNET ASSEMBLY WITH ALIGNMENT TEMPLATE INDEX MARK.
1
1
1. Tighten the fasteners and remove the alignment template.
Note
Use a flat end hex key to tighten the magnet assembly fasteners to a torque of 2.37 N•m (21 lbf•in) for 4 mm screws, and
5.08 N•m (45 lbf•in) for 5 mm screws. For added security, especially in vibrating services, blue (medium) threadlocker may be
used on the fasteners.
2. Remove the plug (R1/8) from the back of the DVC6200 housing. This pneumatic output port on the DVC6200 lines
up with the integral actuator pneumatic port. See figure 8.