Quick Start Guide
D103556X012
DVC6200 Digital Valve Controllers
July 2017
44
Wiring Configuration Option for Solenoid Valve Testing
(DVC6200 SIS Only)
The DVC6200 SIS device can be used to provide a momentary signal interruption to the solenoid valve for solenoid
valve testing. To do this, the OUT terminals in the digital valve controller are used in series with the solenoid valve, as
shown in figure 37.
D Connect the solenoid valve wires from the Logic Solver to the DVC6200 SIS OUT terminals.
D Connect the solenoid valve wires to the DVC6200 SIS OUT terminals.
Figure 37. Wiring the Solenoid Valve for Solenoid Valve Testing through (DVC6200 SIS De-Energize to Trip
pneumatics shown)
 1 SEE NOTE ON PAGE 43
-
+
24 VDC
A
E1638
S
B
- +
Out
1
MONITORING
LINE
CONTROL LINE
Notes
This wiring configuration option requires DVC6200 SIS FW 7 or later.
The Transmitter/Switch selection on the printed wiring board (PWB) must be set to 'Switch'. See figure 22 on page 28.
The solenoid valve circuit must be 30 VDC or less, with a maximum current of 1 amp.
In the DVC6200 SIS configuration, the Output Terminal must be set to 'Solenoid Valve Test'.
Refer to page 26 for loop wiring.
Loss of LOOP power to the DVC6200 SIS will take the OUT circuit to the open state.
Proceed to Step 4—Configure the Digital Valve Controller on page 33.
SIS
Emerson Automation Solutions
Marshalltown, Iowa 50158 USA
Sorocaba, 18087 Brazil
Cernay, 68700 France
Dubai, United Arab Emirates
Singapore 128461 Singapore
www.Fisher.com
The contents of this publication are presented for informational purposes only, and while every effort has been made to ensure their accuracy, they are not
to be construed as warranties or guarantees, express or implied, regarding the products or services described herein or their use or applicability. All sales are
governed by our terms and conditions, which are available upon request. We reserve the right to modify or improve the designs or specifications of such
products at any time without notice.
E 2012, 2017 Fisher Controls International LLC. All rights reserved.
Neither Emerson, Emerson Automation Solutions, nor any of their affiliated entities assumes responsibility for the selection, use or maintenance
of any product. Responsibility for proper selection, use, and maintenance of any product remains solely with the purchaser and end user.
Fisher, FIELDVUE, ValveLink, and THUM are marks owned by one of the companies in the Emerson Automation Solutions business unit of Emerson Electric
Co. Emerson Automation Solutions, Emerson, and the Emerson logo are trademarks and service marks of Emerson Electric Co. HART and the HART logo are
registered trademarks of FieldComm Group. FOUNDATION fieldbus and the Fieldbus logo are trademarks of FieldComm Group. The PROFIBUS logo is a
mark owned by PROFIBUS Nutzerorganisation e.V. All other marks are the property of their respective owners.

Other manuals for Emerson Fisher FIELDVUE DVC6200 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Emerson Fisher FIELDVUE DVC6200 Series and is the answer not in the manual?

Emerson Fisher FIELDVUE DVC6200 Series Specifications

General IconGeneral
BrandEmerson
ModelFisher FIELDVUE DVC6200 Series
CategoryController
LanguageEnglish

Related product manuals