1 System readiness
Confirm HART revision capability
• If using HART-based control or asset management systems, confirm the
HART capability of those systems prior to transmitter installation. Not all
systems are capable of communicating with HART Revision 7. This
transmitter can be configured for either HART Revision 5 or 7.
• For instructions on how to change the HART revision of your transmitter,
see Switch HART revision mode.
1.1 Confirm correct device driver
• Verify the latest device driver (DD/DTM
™
) is loaded on your systems to
ensure proper communications.
• Download the latest device driver at Emerson.com or
Fieldcommgroup.org.
Rosemount 3051 device revisions and drivers
Table 1-1 provides the information necessary to ensure you have the correct
device driver and documentation for your device.
Table 1-1: Rosemount 3051 with 4-20mA HART Protocol Device Revisions
and Files
Release
date
Device identification Device Driver
identification
Review
Instructions
Review
Functio
nality
NAMUR
hardwa
re
Revisio
n
(1)
(2)
(1)
HART
Softwa
re
Revisio
n
(3)
HART
univers
al
revisio
n
Device
Revisio
n
(4)
Rosemount
2088,
2090P, and
2090F
Pressure
Transmitter
s
Change
descrip
tion
Aug-16 1.1.xx 1.0.xx 3 7 10 with HART
and 1–5 Vdc
Low Power
Protocol
Reference
Manual
with 4–20
mA HART
and 1–5 Vdc
Low Power
Protocol
(5)
5 9
Jan-13 N/A 1.0.xx 1 7 10
(6)
5 9
February 2019 Quick Start Guide
Quick Start Guide 3