Power line connection
6.
238
Ref.1912
DDS
HARDWARE
· 232 ·
6.5 Mains filter
In order for the FAGOR DDS system to meet the European Directive on
Electromagnetic Compatibility 2014/30/EU, a mains filter must be installed
against electromagnetic disturbances. The optional filters provided by
FAGOR ensure the compliance of the DDS system itself with the currently
effective directive.
To install it, it must be properly connected to ground and the wires
connecting to the power supply module must be as short as possible.
They may be installed either horizontally or vertically. The three-phase line
is connected to the terminals on top of the module and the load (power
supply or compact drive) to those at the bottom. See the label on the front
panel showing these terminals in full detail. See figure
F. H6/3.
Table T. H6/5 indicates the proper filter to be installed depending on the
power supply or compact drive being used in the DDS system.
For further information on mains filters, see section
4.1 Mains filters of this
manual.
MANDATORY. ALWAYS install mains filters from the FAGOR catalog when
installing the DDS drive system.
INFORMATION. This does not guarantee the compliance with such CE
Directive on Electromagnetic Compatibility regarding the machine
because
it may have other devices that could cause disturbances.
F. H6/3
Installation of the mains filter.
L3 L2 L1
MAINS
3 Phase RFI Filter
Type:
L3' L2' L1'
LOAD
CURRENT:
75A
@
MPC-4x...
POWER SUPPLY
L1'
L2'
L3'
PE
MPC-4x...
MAINS FILTER
top view
3-ph - MAINS
MAINS FILTER
bottom view
L1 L2 L3
L1
L2
L3
L1
L2
L3
PE
NOTE. It is not required that the cables
be shielded.
MANDATORY. Install the mains filter between the transformer or auto-
transformer and the - KM1 power contactor.
T. H6/5 Mains filter selection according to the power supply or compact
drive installed.
Module Mains filter
PS-25B4, XPS-25, RPS-20 MAIN FILTER 42A-A
RPS-45 MAIN FILTER 75A-A
PS-65A, XPS-65, RPS-75 MAIN FILTER 130A-A
RPS-80 MAIN FILTER 180A-A
ACD/SCD/CMC X.XX MAIN FILTER 42A-A