EasyManuals Logo
Home>Fujitsu>Air Conditioner>AB12

Fujitsu AB12 User Manual

Fujitsu AB12
199 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #90 background imageLoading...
Page #90 background image
Error Code
Error Code
Error contents
Model data abnormal
No error
Power supply frequency error
EEPROM access error
EEPROM deletion error
Room temperature themistor error
Indoor unit heat exchanger themistor
Indoor unit heat exchanger themistor
Indoor unit heat exchanger themistor
Blower tempearture themistor error
Drain abnormal
Room tempearture abnormal
Indoor unit fan error
Transmission error
Node setting error
Parallel communication error
8-3 REMOTE CONTROL UNIT
MASTER
CONTROL
FAN
CONTROL
TIMER
MODE
TEMP./DAY
SET TIME
CLOCK ADJUST
START/STOP
SET
DAY OFF
ZONE
ENERGY SAVE
MASTER
CONTROL
FAN
CONTROL
TIMER
MODE
TEMP./DAY
SET TIME
CLOCK ADJUST
START/STOP
SET
DAY OFF
ZONE
ENERGY SAVE
COOL
CLOCK
C
NON STOP
When EE : EE blinks at the current time display, there
is an error inside the air conditioner. If the SET TIME
button ( ) and SET TEMP./DAY button ( ) are pressed
simultaneously for more than three seconds, the self
diagnosis check will start and the error contents will
be displayed at the current time display. In addition,
the remote controller address will be displayed at the
current time display. In addition, the remote controller
address will be displayed below. When the operation
lamp lights, press the START/STOP button and after
operation lamp goes off, perform the same operation.
Outdoor unit error
(middle) error
(inlet) error
(outlet) error
– 90
SET

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu AB12 and is the answer not in the manual?

Fujitsu AB12 Specifications

General IconGeneral
BrandFujitsu
ModelAB12
CategoryAir Conditioner
LanguageEnglish

Related product manuals