4. AUTO CHANGEOVER OPERATION
When the air conditioner is set to the AUTO mode by remote control, operation starts in the optimum
mode from among the HEATING, COOLING and MONITORING modes. During operation, the
optimum mode is automatically swiched in accordance with temperature changes. The temperature
can be set between 64°F(18°C) and 88°F(30°C) in 2 degF(1 degC) steps.
When operation starts, only the indoor fan is operated for 1 minute. (Air flow mode: S- Lo)
After 1 minute, depends on the room temperature and outdoor unit's operarion mode,
the operation mode is selected in accordance with the table below.
( Table 4 : Operation mode selection table )
When COOLING was selected at , the same operation as COOLING OPERATION is performed.
When HEATING was selected at , the same operation as HEATING OPERATION is performed.
When the compressor was stopped for 6 consecutive minutes by the temperature control function
after the COOLING or HEATING operation mode was selected at above, operation is switched
to MONITORING and the operation mode is selected again.
1
1
2
3
1
4
1
01-04
Room temperature :TR
Operation mode
TR > Ts +3.6 degF
(2 degC)
Ts +3.6 degF > TR
(2 degC)
=
=
Ts +3.6 degF > TR > Ts-3.6 degF
(2 degC) (2 degC)
Cooling
Monitoring
Heating
Ts : Setting temperature