6. Capacity compensation rate for pipe length and height
difference
Height difference H
Indoor unit is higher than outdoor unit *
1
Indoor unit is lower than outdoor unit *
2
Indoor unit
Indoor unit
Connection pipe
Outdoor unit
Outdoor unit
Connection pipe
H H
6-1. Model: AOU9RL2
NOTE: Values mentioned in the table are calculated based on the maximum capacity.
COOLING
Pipe length
m
5 7.5 10 15 20
ft 17 25 33 50 67
Height difference H
Indoor unit is higher than outdoor
unit *
1
15 50 — — — 0.901 0.920
10 33 — — 0.969 0.916 0.936
7.5 25 — 0.988 0.973 0.919 0.939
5 17 1.003 0.992 0.976 0.923 0.943
0 0 1.011 1.000 0.984 0.931 0.951
Indoor unit is lower than outdoor
unit *
2
-5 -17 1.011 1.000 0.984 0.931 0.951
-7.5 -25 — 1.000 0.984 0.931 0.951
-10 -33 — — 0.984 0.931 0.951
-15 -50 — — — 0.931 0.951
HEATING
Pipe length
m
5 7.5 10 15 20
ft 17 25 33 50 67
Height difference H
Indoor unit is higher than outdoor
unit *
1
15 50 — — — 0.904 0.898
10 33 — — 0.976 0.904 0.898
7.5 25 — 1.000 0.976 0.904 0.898
5 17 1.014 1.000 0.976 0.904 0.898
0 0 1.014 1.000 0.976 0.904 0.898
Indoor unit is lower than outdoor
unit *
2
-5 -17 1.009 0.995 0.971 0.900 0.894
-7.5 -25 — 0.993 0.968 0.898 0.892
-10 -33 — — 0.966 0.895 0.889
-15 -50 — — — 0.886 0.880
- 33 -
6-1. Model: AOU9RL2
6. Capacity compensation rate for pipe length and height difference
OUTDOOR UNIT
AOU9-12RL2
OUTDOOR UNIT
AOU9-12RL2