6-2. Model: AOU12RL2
NOTE: Values mentioned in the table are calculated based on the maximum capacity.
COOLING
Pipe length
m
5 7.5 10 15 20
ft 17 25 33 50 67
Height difference H
Indoor unit is higher than outdoor
unit *
1
15 50 — — — 0.872 0.882
10 33 — — 0.953 0.887 0.897
7.5 25 — 0.988 0.957 0.890 0.900
5 17 1.023 0.992 0.961 0.894 0.904
0 0 1.031 1.000 0.969 0.901 0.911
Indoor unit is lower than outdoor
unit *
2
-5 -17 1.031 1.000 0.969 0.901 0.911
-7.5 -25 — 1.000 0.969 0.901 0.911
-10 -33 — — 0.969 0.901 0.911
-15 -50 — — — 0.901 0.911
HEATING
Pipe length
m
5 7.5 10 15 20
ft 17 25 33 50 67
Height difference H
Indoor unit is higher than outdoor
unit *
1
15 50 — — — 0.944 0.935
10 33 — — 0.982 0.944 0.935
7.5 25 — 1.000 0.982 0.944 0.935
5 17 1.014 1.000 0.982 0.944 0.935
0 0 1.014 1.000 0.982 0.944 0.935
Indoor unit is lower than outdoor
unit *
2
-5 -17 1.009 0.995 0.977 0.940 0.930
-7.5 -25 — 0.993 0.975 0.937 0.928
-10 -33 — — 0.972 0.935 0.925
-15 -50 — — — 0.926 0.916
- 34 -
6-2. Model: AOU12RL2
6. Capacity compensation rate for pipe length and height difference
OUTDOOR UNIT
AOU9-12RL2
OUTDOOR UNIT
AOU9-12RL2