EasyManuals Logo
Home>Fujitsu>Air Conditioner>ASU9RLF1

Fujitsu ASU9RLF1 Service Manual

Fujitsu ASU9RLF1
100 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #89 background imageLoading...
Page #89 background image
SERVICE PARTS INFORMATION 1
PSI
Compressor
Diagnosis method of Compressor ( If Outdoor Unit LED displays Error, refer to Trouble shooting )
Does not start up
Is there open or loose connection
cable?
Check Filter PCB, Main PCB,
connection of Compressor,and winding
resistance. (Refer to the next page).
>> If there is no failure, the defect of
Compressor is considered (Locked
compressor due to clogged dirt or
less oil)
Replace Compressor
Stops soon after starting up
Is there open or loose connection
cable?
Is Gas Pipe Valve open?
(Low Pressure is too low)
Check if Strainer is clogged.
(
PARTS INFORMATION 3)
Abnormal noise
Check if vibration noise by
loose bolt or contact noise
of piping is happening.
Defective Compressor
can be considered.
(due to inside dirt clogging
or broken component)
>> If there is no failure, the defect of Compressor can be
considered. (Compression part broken or valve defective.)
Check if Refrigerant is leaking.
(Recharge Refrigerant)
Replace Compressor
Replace Compressor
Check Filter PCB, Main PCB,
connection of Compressor,and winding
resistance. (Refer to the next page).
PSI
02-49
2-4 SERVICE PARTS INFORMATION

Table of Contents

Other manuals for Fujitsu ASU9RLF1

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu ASU9RLF1 and is the answer not in the manual?

Fujitsu ASU9RLF1 Specifications

General IconGeneral
BrandFujitsu
ModelASU9RLF1
CategoryAir Conditioner
LanguageEnglish

Related product manuals