3. Fan control
Tr: Room temperature
Ts: Setting temperature
3-1. Indoor fan control
¢ Compact cassette type
 Fan speed
Indoor fan speed is defined as below.
Operation mode Fan mode
Speed (rpm)
07 09 12 14 18
Heating
HIGH 590 590 650 830 830
MED+ 570 570 620 770 770
MED 540 540 580 730 730
LOW 490 490 520 630 630
QUIET 440 440 460 500 500
Cool air
prevention
400 400 400 400 400
S-LOW 300 300 300 300 300
Cooling/Fan
HIGH 590 590 650 730 730
MED 540 540 580 630 630
LOW 490 490 520 540 540
QUIET 440 440 460 460 460
Soft quiet
400*
1
400*
1
400*
1
400*
1
400*
1
S-LOW
300*
2
300*
2
300*
2
300*
2
300*
2
Dry
X zone: 440
J zone: 440
X zone: 440
J zone: 440
X zone: 460
J zone: 460
X zone: 460
J zone: 460
X zone: 460
J zone: 460
*1: Fan mode only
*2: Cooling mode only
 Fan operation
Airflow can be switched in 5 steps such as AUTO, QUIET, LOW, MED, HIGH while indoor unit fan
only runs.
When fan mode is set at AUTO, it operates on MED fan speed.
3-1. Indoor fan control
- (04-22) - 3. Fan control
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS

Table of Contents

Other manuals for Fujitsu ASY50-KM

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu ASY50-KM and is the answer not in the manual?

Fujitsu ASY50-KM Specifications

General IconGeneral
BrandFujitsu
ModelASY50-KM
CategoryAir Conditioner
LanguageEnglish

Related product manuals