11. Setting results are displayed after data transmission.
12. Press the
button to return to the 2-wire remote controller address selection screen of step
9. If setting has been completed, press the FAN button to return to the Menu 2-F1 item se-
lection screen.

Setting up each indoor unit
Repeat the procedure from step 1 to 6, and set up the indoor units requiring function setting.

Resetting the power after setting up function of all indoor units
NOTES:
• If the reset is not performed, function cannot be read correctly.
• After all the functions have been set, the circuit breaker needs to be switched off for at least 2
minutes.
– After the 2 minutes has passed, power can be restored.
– The set function is stored in the PCB and will remain in memory even when the power of in-
door unit is turned off.
However setting function is effective after disconnecting the power supply and then recon-
necting it.
• Record the latest configuration of the indoor unit function setting on a label, and put the label on
the unit so it can be used for after-sales service operations.
1-4. Indoor unit (setting by simple remote controller) - (05-37) - 1. Function settings (for indoor unit)
FIELD
WORKING
FIELD
WORKING