1-1. Indoor unit
¢
Compact cassette type
Model name AUXG07KVLA AUXG09KVLA AUXG12KVLA AUXG14KVLA
Power supply 1Ø 230 V~ 50 Hz
Available voltage range 198—264 V
Capacity kW class 2.0 2.5 3.5 4.0
Input power W 18 23 28
Running current A 0.15 0.19 0.22
Fan
Airflow rate
Cooling
HIGH
m
3
/h
540 610 680
MED 490 530 580
LOW 440 470 490
QUIET 390 410 410
Heating
HIGH 540 610 790
MED 490 530 680
LOW 440 470 580
QUIET 390 410 450
Type × Qty Turbo fan × 1
Motor output W 54
Sound pressure level*
Cooling
HIGH
dB (A)
33 37 38
MED 31 34 35
LOW 29 31 32
QUIET 27 28 29
Heating
HIGH 34 37 43
MED 32 34 38
LOW 29 31 34
QUIET 27 29 30
Sound power level
Cooling
dB (A)
46 49 50
Heating 47 49 55
Heat exchanger type
Dimensions (H × W × D) mm
Main 1: 210 × 1,310 × 13.3
Main 2: 210 × 1,250 × 13.3
Fin pitch mm 1.2
Rows × Stages
Main 1: 1 × 10
Main 2: 1 × 10
Pipe type Copper tube
Fin type Aluminum
Dimensions
(H × W × D)
Net
mm
245 × 570 × 570
Gross 265 × 730 × 625
Weight
Net
kg
15
Gross 19
Connection pipe
Size
Liquid
mm (in)
Ø6.35 (Ø1/4)
Gas Ø9.52 (Ø3/8)
Method Flare
Drain hose
Material PVC
Tip diameter mm Ø25 (I.D.), Ø32 (O.D.)
Operation range
Cooling
°C 18 to 32
%RH 80 or less
Heating °C 16 to 30
Cassette grille
(Grid type: Option)
Model name
UTG-UFYF-W
Material Polystyrene
Color
White
Approximate color of Munsell 9PB 9.1/0.2
Dimensions
(H × W × D)
Net
mm
49 × 620 × 620
Gross 120 × 765 × 755
Weight
Net
kg
2.3
Gross 4.5
NOTES:
• The protective function might work when using it outside the operation range.
• *: Sound pressure level:
– These are the measured values in the manufacturer’s anechoic chamber.
– Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
1-1. Indoor unit
- (01-1) - 1. Specifications
GENERAL
INFORMATION
GENERAL
INFORMATION