EasyManuals Logo
Home>Fujitsu>Air Conditioner>ASY50-KM

Fujitsu ASY50-KM Design & Technical Manual

Fujitsu ASY50-KM
567 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #478 background imageLoading...
Page #478 background image
1. Specifications
Type Inverter heat pump
Model name AOYG36KBTA5
Power source 230 V 50 Hz
Available voltage range 198—264V
Standard combination of indoor unit
Wall mounted
ASYG07KMCC ×5
Capacity
Cooling
Rated
kW 9.5
Btu/h 32,400
Min.—Max.
kW 3.0—11.0
Btu/h 10,200—37,500
Heating
Rated
kW 10.6
Btu/h 36,200
Min.—Max.
kW 3.5—12.0
Btu/h 11,900—40,900
Input power
Cooling
Rated
kW
2.50
Max. 3.45
Heating
Rated 2.36
Max. 3.25
Current
Cooling Rated
A
11.1
Heating Rated 10.9
EER Cooling
kW/kW
3.8
COP Heating 4.5
Starting current A 11.1
Maximum operating current *
1
A 20.0
Fan
Type × Q'ty Propeller × 1
Airflow rate
Cooling
m
3
/h
2,450
Heating 2,900
Motor output W 49
Sound pressure level *
2
Cooling
dB (A)
52
Heating 55
Heat exchanger
Dimension (H x W x D)
mm
Main1: 840 × 873 × 18.19
Main2: 840 × 843 × 18.19
Main3: 840 × 784 × 18.19
Fin pitch 1.45
Rows × Stages
Main1: 1 × 40
Main2: 1 × 40
Main3: 1 × 40
Pipe type (Material) Copper tube
Fin type (Material) Aluminum
Compressor
Type × Quantity DC twin rotary × 1
Motor output W 1,450
Refrigerant
Type R32 (675)
Charge g 2,500
Refrigerant oil
Type RmM68AF
Amount
cm
3
800
Enclosure
Material Steel sheet
Color
Beige
(Approximate color of Munsell 10YR 7.5/1.0 NN)
Dimensions
(H x W x D)
Net
mm
884 × 820 × 315
Gross 1,058 × 1,027 × 445
Weight
Net
kg
59
Gross 69
Connection pipe
Size
Liquid
mm (in)
Ø6.35 (Ø1/4) × 5
Gas Ø9.52 (Ø3/8) × 3 + Ø12.7 (Ø1/2) × 2
Method Flare
Pre-charge length (Total)
m
40
Maximum length (Total) 75
Maximum length (Each) 25
Minimum length (Total) 15
Minimum length (Each) 2.5
Maximum height difference between outdoor unit and each in-
door units.
15
Maximum height difference between indoor units. 10
Drain hose
Material PP
Tip diameter mm Ø13.0 (I.D.), Ø16.0 to Ø16.8 (O.D.)
Operation range
Cooling
°C
-10 to 46
Heating -15 to 24
NOTES:
• Specifications are based on the following conditions:
– Power source of specifications: 230 V
– Pipe length: 5 m, Height difference: 0 m [Outdoor unit—Indoor unit]
– Cooling: Indoor temperature of 27.0 °CDB/19.0 °CWB, and outdoor temperature of 35 °CDB/24.0 °CWB.
– Heating: Indoor temperature of 20.0 °CDB/15.0 °CWB, and outdoor temperature of 7.0 °CDB/6.0 °CWB.
• *1: Maximum operating current is the total current of the indoor unit and the outdoor unit.
• *2: Sound pressure level
– Measured values in manufacturer’s anechoic chamber.
– Because of the surrounding sound environment, the sound levels measured in actual installation conditions might be higher than the specified values here.
• For other combination, refer to the combination table.
• The protective function might work when using it outside the operation range.
• This data is based on EN 14511 standard.
- 470 -
1. Specifications
OUTDOOR UNIT
AOYG36KBTA5
OUTDOOR UNIT
AOYG36KBTA5

Table of Contents

Other manuals for Fujitsu ASY50-KM

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu ASY50-KM and is the answer not in the manual?

Fujitsu ASY50-KM Specifications

General IconGeneral
BrandFujitsu
ModelASY50-KM
CategoryAir Conditioner
LanguageEnglish

Related product manuals