EasyManuals Logo
Home>Fujitsu>Air Conditioner>ASYG07KMCC

Fujitsu ASYG07KMCC User Manual

Fujitsu ASYG07KMCC
567 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #191 background imageLoading...
Page #191 background image
11. Safety devices
Indoor unit
type
Model name PCB* fuse Fan motor thermal protector
Terminal
thermal
fuse
Float
switch
Compact
cassette
AUXG07KVLA
250 V, 5 A
Activate: 100 ±15 °C
Fan motor stop
Reset: 95 ±10 °C
Fan motor restart
―
â—‹
AUXG09KVLA
AUXG12KVLA
AUXG14KVLA
AUXG18KVLA
AUXG22KVLA
Mini duct
ARXG07KSLAP
Activate: 135 ±15 °C
Fan motor stop
Reset: 105 ±15 °C
Fan motor restart
ARXG09KSLAP
ARXG12KSLAP
ARXG14KSLAP
ARXG18KSLAP
Slim duct
ARXG07KLLAP
ARXG09KLLAP
ARXG12KLLAP
ARXG14KLLAP
ARXG18KLLAP
Activate: 135 ±15 °C
Fan motor stop
Reset: 115 ±15 °C
Fan motor restart
Medium static
pressure duct
ARXG22KMLB
Activate: 135 ±15 °C
Fan motor stop
Reset: 115 ±15 °C
Fan motor restart
―
ARXH22KMTAP
Activate: 115 ±15 °C
Fan motor stop
Reset: 70 °C
Fan motor restart
â—‹
- 183 -
11. Safety devices
4-5 UNIT
MULTI-SPLIT TYPE
4-5 UNIT
MULTI-SPLIT TYPE

Table of Contents

Other manuals for Fujitsu ASYG07KMCC

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu ASYG07KMCC and is the answer not in the manual?

Fujitsu ASYG07KMCC Specifications

General IconGeneral
BrandFujitsu
ModelASYG07KMCC
CategoryAir Conditioner
LanguageEnglish

Related product manuals