11. Electrical characteristics
Model name AOYG36KBTA5
Power supply
Voltage V 230 ~
Frequency Hz 50
Maximum operating current *
1
A 20.0
Starting current A 11.1
Wiring spec. *
2
Main fuse (Circuit breaker) current A 25
Power cable
mm
2
2.5
Connection
cable *
3
Cross-sectional area 1.5
Limited wiring length m 26
*
1
: Maximum operating current is the total current of the indoor unit and the outdoor unit.
*
2
: Selected sample based on Japan Electrotechnical Standards and Codes Committee E0005. As
the regulations of wire size and circuit breaker differ in each country or region, select appropriate de-
vices complied to the regional standard.
*
3
: This is the wiring length in case voltage descent is less than 2%. When the wiring length be-
comes longer, select the wiring of a more larger diameter.
- 539 -
11. Electrical characteristics
OUTDOOR UNIT
AOYG36KBTA5
OUTDOOR UNIT
AOYG36KBTA5