13-2. Outdoor unit low noise operation function (option)
Change the outdoor unit low noise operation by using this setting.
CAUTION
• When the low noise operation function is working, cooling and heating capacity will de-
crease.
• When changing the settings, explain to the customer beforehand that the capacity decreas-
es.
NOTES:
• When SET1-4 is OFF, optional Central remote controller is required to use this function.
• When SET1-4 is ON, “Operation” and “Non-operation” mode of this function cannot be
switched from the Central remote controller.
SET1-4 Setting Factory setting
ON Continuous operation
OFF
Follow the Central remote controller
settings
♦
SET2-1 Setting Factory setting
ON Lower
OFF Low ♦
13-3. Current limit function
Current value can be limited to meet specific current requirements.
NOTE: When changing this setting, explain to the customer beforehand that the capacity decreas-
es.
SET2-3 SET2-4 Current Factory setting
OFF OFF Full ♦
ON OFF 16.0 A
OFF ON 12.0 A