14. Check and test
14-1. Check run
• The check run is a function to screen and detect any wiring errors.
• After carrying out the check run, you can use the automatic wiring correction function to correct the
wiring.
• Normal operation is possible without using the check run. In this case, use the test run or forced
cooling function of the indoor unit to confirm any wiring errors.
¢
Things to confirm before starting the check run
To ensure safety, check that the following work, inspections and operations have been complet-
ed.
Check item Check column
1
Check that all work on the piping connecting the outdoor unit, indoor units has
been completed.
2
Check that all work on the wiring connecting the outdoor unit, indoor units has
been completed.
3
Is there a gas leakage? (At pipe connections [flange connections and brazed
areas])
4 Is the system charged with the specified volume of refrigerant?
5 Is a breaker installed at the power supply cable of outdoor unit?
6
Are the wires connected to the terminals without looseness, and in accordance
with the specifications?
7 Is the 3-way valve of the outdoor unit open? (Gas pipe and liquid pipe)
8 Is the power supply connected for more than 12 hours?
¢
Restrictions applicable when performing the check run
• When the check run starts, all indoor units connected to the outdoor unit will start to run automati-
cally. During the check run, you cannot check the operation of the indoor units separately. After
the check run, check the operation of the indoor units separately in normal operation.
• The check run can be used when the temperature is within the operable temperature of the air
conditioner.
• In the check run, the air conditioner will automatically switch between cooling and heating depend-
ing on the external temperature and internal temperature.
• The check run can be completed in about 30 minutes (cooling) or about 1 hour (heating), but may
take more depending on the external and internal temperature conditions etc.
• Do not conduct the check run with all the windows in the room closed.
Otherwise the room temperature could get too low or too high.
• Depending on the difference of the room temperature of each room, a judgment may be impossi-
ble.
• Check run is a special operation so there may be a noise louder than the normal refrigerant flow
sound or a creaking noise.
- 545 -
14-1. Check run
14. Check and test
OUTDOOR UNIT
AOYG36KBTA5
OUTDOOR UNIT
AOYG36KBTA5

Table of Contents

Other manuals for Fujitsu ASYG07KMCC

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Fujitsu ASYG07KMCC and is the answer not in the manual?

Fujitsu ASYG07KMCC Specifications

General IconGeneral
BrandFujitsu
ModelASYG07KMCC
CategoryAir Conditioner
LanguageEnglish

Related product manuals