3. Troubleshooting without error code
3-1. Indoor unit—No power
Forecast of cause
Power supply failure
External cause
Electrical components defective
Attention
An indoor unit and an outdoor unit are connected, and a power supply has be connected to an in-
door unit.
Check point 1. Check installation condition
• Is the circuit breaker on or off?
• Check loose or removed connection cable.
-> If abnormal condition is found, correct it by referring to the installation manual or the “DESIGN &
TECHNICAL MANUAL”.
↓
Check point 2. Check external cause at indoor and outdoor (voltage drop or noise)
• Instant drop: Check if there is a large load electric apparatus in the same circuit.
• Momentary power failure: Check if there is a defective contact or leak current in the power sup-
ply circuit.
• Noise: Check if there is any equipment causing harmonic wave near electric line. (Neon bulb or
electric equipment that may cause harmonic wave)
Check the complete insulation of grounding.
↓
Check point 3. Check electrical components
Check the voltage of power supply.
Check if AC 198 to 264 V appears at outdoor unit terminal 1—2.
-> If no, go to "Check point 1" and "Check point 2".
↓
• Check fuse in filter PCB.
If fuse is open, check if the wiring between terminal and filter PCB is loose, and replace fuse.
• Check varistor in filter PCB.
If varistor is defective, there is a possibility of an abnormal power supply.
Check the correct power supply and replace varistor.
Upon checking the normal power supply, replace varistor.
↓
End
3-1. Indoor unit—No power - (03-58) - 3. Troubleshooting without error code
TROUBLESHOOTING
TROUBLESHOOTING