1. Rotation number control of compressor
1-1. Cooling operation
A sensor (room temperature thermistor) built in the indoor unit body will usually perceive difference
or variation between a set temperature and present room temperature, and controls the operation
rotation number of the compressor.
• If the room temperature is 6.0°C higher than a set temperature, the operation rotation number of
the compressor will attain to maximum performance.
• If the room temperature is 1.0°C lower than a set temperature, the compressor will be stopped.
• When the room temperature is within the range of +6.0°C to -1.0°C of the setting temperature, the
rotation number of the compressor is controlled within the range shown in the table below. Howev-
er, the maximum rotation number is limited in the range shown in the figure below based on the
indoor fan mode and the outdoor temperature.
¢ Compact cassette type
• Rotation number range of compressor
Unit: rps
Connected model name Minimum rotation number Maximum rotation number
AOHG14KBTA2 12 110
AOHG18KBTA2 8 120
• Limit of maximum speed based on outdoor temperature
A zone
26°C
B zone
C zone
D zone
23°C
20°C
Unit: rps
– Model: AOHG14KBTA2
Model name
Outdoor
temperature
zone
Indoor unit fan mode
HIGH MED LOW QUIET
AUXG07KVLA
AUXG09KVLA
AUXG12KVLA
A zone 96 67 58 50
B zone 103 77 67 58
C zone 110 96 83 72
D zone 110 110 110 110
AUXG14KVLA
A zone 96 67 58 44
B zone 103 77 67 50
C zone 110 96 83 62
D zone 110 110 110 110
1-1. Cooling operation - (04-1) - 1. Rotation number control of compressor
CONTROL AND
FUNCTIONS
CONTROL AND
FUNCTIONS