1-2. Heating operation
A sensor (room temperature thermistor) built in indoor unit body will usually perceive difference or
variation between setting temperature and present room temperature, and controls operation rota-
tion number of compressor.
If the room temperature is 6.0°C lower than a set temperature, the operation rotation number of
compressor will attain to maximum performance.
If the room temperature is 1.0°C higher than a set temperature, the compressor will be stopped.
When the room temperature is within the range of +1.0°C to -6.0°C of the setting temperature, the
rotation number of compressor is controlled within the range shown below.
Rotation number range of compressor
Unit: rps
Connected model name Minimum rotation number Maximum rotation number
AOHG14KBTA2 12 110
AOHG18KBTA2 8 120
1-2. Heating operation - (04-14) - 1. Rotation number control of compressor