EasyManuals Logo
Home>GE>Relays>b30

GE b30 User Manual

GE b30
626 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #373 background imageLoading...
Page #373 background image
GE Multilin B30 Bus Differential System 6-17
6 ACTUAL VALUES 6.3 METERING
6
f) FREQUENCY
PATH: ACTUAL VALUES  METERING SOURCE SRC 1  FREQUENCY
The metered frequency values are displayed in this menu. The "SRC 1" text will be replaced by whatever name was pro-
grammed by the user for the associated source (see
SETTINGS  SYSTEM SETUP  SIGNAL SOURCES).
SOURCE FREQUENCY is measured via software-implemented zero-crossing detection of an AC signal. The signal is either a
Clarke transformation of three-phase voltages or currents, auxiliary voltage, or ground current as per source configuration
(see the
SYSTEM SETUP  POWER SYSTEM settings). The signal used for frequency estimation is low-pass filtered. The
final frequency measurement is passed through a validation filter that eliminates false readings due to signal distortions and
transients.
6.3.5 TRACKING FREQUENCY
PATH: ACTUAL VALUES  METERING  TRACKING FREQUENCY
The tracking frequency is displayed here. The frequency is tracked based on the selection of the reference source with the
FREQUENCY AND PHASE REFERENCE setting in the SETTINGS  SYSTEM SETUP  POWER SYSTEM menu. See the Power
System section of chapter 5 for details.
6.3.6 FLEXELEMENTS
PATH: ACTUAL VALUES  METERING  FLEXELEMENTS FLEXELEMENT 1(8)
The operating signals for the FlexElements are displayed in pu values using the following definitions of the base units.
FREQUENCY
SRC 1
SRC 1 FREQUENCY:
0.00 Hz
TRACKING FREQUENCY
TRACKING FREQUENCY:
60.00 Hz
FLEXELEMENT 1
FLEXELEMENT 1
OpSig: 0.000 pu
Table 6–2: FLEXELEMENT BASE UNITS
BUS DIFFERENTIAL
RESTRAINING CURRENT
(Bus Diff Mag)
I
BASE
= maximum primary RMS value of the +IN and –IN inputs
(CT primary for source currents, and bus reference primary current for bus differential currents)
BUS DIFFERENTIAL
RESTRAINING CURRENT
(Bus Rest Mag)
I
BASE
= maximum primary RMS value of the +IN and – IN inputs
(CT primary for source currents, and bus reference primary current for bus differential currents)
DCmA BASE = maximum value of the
DCMA INPUT MAX setting for the two transducers configured
under the +IN and –IN inputs.
FREQUENCY f
BASE
= 1 Hz
PHASE ANGLE ϕ
BASE
= 360 degrees (see the UR angle referencing convention)
POWER FACTOR PF
BASE
= 1.00
RTDs BASE = 100°C
SOURCE CURRENT I
BASE
= maximum nominal primary RMS value of the +IN and –IN inputs
SOURCE POWER P
BASE
= maximum value of V
BASE
× I
BASE
for the +IN and –IN inputs
SOURCE VOLTAGE V
BASE
= maximum nominal primary RMS value of the +IN and –IN inputs