9 SPECIFICATIONS
Model : GT6000 GT10000
Ratings
Voltage Amperes (VA) with computer type load : 6000 10000
Watts (W) with resistive load : 4200 7000
Input thermal circuit breaker (A) : 30 63
Internal input fuse 250V, slow (A) : 30 30*2
Input converter
AC input voltage : Nominal: 230 V
AC input voltage range : 84 - 276 V (84-175V with load de-rating)
input >276 Vac: UPS switches to battery operation
Input current waveform : sine wave
Input current (A) at nominal input voltage : 20.6 34.6
Input power factor : > 0.97
Input frequency range : 40 - 70 Hz
Inrush current : 60A
Output converter
AC output voltage : 220 / 230 / 240 V (selectable)
AC output voltage tolerance : ± 2%
Output frequency : 50/60 Hz, auto selection
Output frequency range : nominal ± 5% with mains synchronizing
Output waveform : sine wave
Harmonic distortion : < 3% with linear load, < 8% with non-linear full load
Power factor : 0.7
Crest factor (peak to RMS current) : ≤3:1
Capacity appliance outlets : with 55A Terminal Block
Bypass
AC input voltage range : ± 10% of selected output voltage
Frequency tracking rate : 1Hz/s
Frequency tracking range : ± 5% of selected frequency
Typical transfer time, msec : 0.5
Overload capability : fully protected against overload and short circuits
Overload behaviour during battery operation : 125% during 1 minute
: 150% during 10 seconds
Overload behaviour during bypass operation : depends on rating of thermal circuit breaker
typical: 125% of TCB value for 200 seconds
200% of TCB value for 10 seconds
300% of TCB value for 4 seconds
Batteries (ratings given for 25ºC)
Nominal voltage (Vdc) : 240 240
Number / Ah batteries (in battery kit and battery ext. pack) : 20pcs / 8Ah 20pcs / 8Ah
Type : sealed lead acid, maintenance free
Service life : up to 5 years (depending on use)
Recharge current : 1.2 A
Battery recharge time
(batt. discharged at 100% load) : 5 hours for 90% capacity
Runtime in minutes
at typical load (75%) : 17 9
% VA/Watts
25% 1500/1050 : 66
50% 3000/2100 : 28
75% 4500/3150 : 17
100% 6000/4200 : 12
% VA/Watts :
25% 2500/1750 : 37
50% 5000/3500 : 15
75% 7500/5250 : 9
100% 10000/7000 : - 5
General
Weight UPS kg : 24.5
Dimensions UPS (h
xwxd) : 130x410x660mm
Weight battery pack kg : 67
Dimensions battery pack : 130x410x660mm
Enclosure / protection : steel-plastic / IP20
Environment
Safety : EN 62040-1
Electromagnetic compatibility : EN 62040-2 (2006)
Ambient temperature : 0 to +40ºC
Audible noise at 1 meter : < 55 dB(A), load and temperature dependent
Max. relative humidity : 90% (non-condensing)
Colour : Black - RAL 9005
modifications reserved 25 User manual GT Series 6 - 10 kVA UPS 1.0 (GB)