9 SPECIFICATIONS
Model : GT6000 GT10000
Ratings
Voltage Amperes (VA) with computer type load : 6000 10000
Watts (W) with resistive load : 4200 7000
Input thermal circuit breaker (A) : 30 63
Internal input fuse 250V, slow (A) : 30 30*2
Input converter
AC input voltage : Nominal: 230 V
AC input voltage range : 84 - 276 V (84-175V with load de-rating)
input >276 Vac: UPS switches to battery operation
Input current waveform : sine wave
Input current (A) at nominal input voltage : 20.6 34.6
Input power factor : > 0.97
Input frequency range : 40 - 70 Hz
Inrush current : 60A
Output converter
AC output voltage : 220 / 230 / 240 V (selectable)
AC output voltage tolerance : ± 2%
Output frequency : 50/60 Hz, auto selection
Output frequency range : nominal ± 5% with mains synchronizing
Output waveform : sine wave
Harmonic distortion : < 3% with linear load, < 8% with non-linear full load
Power factor : 0.7
Crest factor (peak to RMS current) : 3:1
Capacity appliance outlets : with 55A Terminal Block
Bypass
AC input voltage range : ± 10% of selected output voltage
Frequency tracking rate : 1Hz/s
Frequency tracking range : ± 5% of selected frequency
Typical transfer time, msec : 0.5
Overload capability : fully protected against overload and short circuits
Overload behaviour during battery operation : 125% during 1 minute
: 150% during 10 seconds
Overload behaviour during bypass operation : depends on rating of thermal circuit breaker
typical: 125% of TCB value for 200 seconds
200% of TCB value for 10 seconds
300% of TCB value for 4 seconds
Batteries (ratings given for 25ºC)
Nominal voltage (Vdc) : 240 240
Number / Ah batteries (in battery kit and battery ext. pack) : 20pcs / 8Ah 20pcs / 8Ah
Type : sealed lead acid, maintenance free
Service life : up to 5 years (depending on use)
Recharge current : 1.2 A
Battery recharge time
(batt. discharged at 100% load) : 5 hours for 90% capacity
Runtime in minutes
at typical load (75%) : 17 9
% VA/Watts
25% 1500/1050 : 66
50% 3000/2100 : 28
75% 4500/3150 : 17
100% 6000/4200 : 12
% VA/Watts :
25% 2500/1750 : 37
50% 5000/3500 : 15
75% 7500/5250 : 9
100% 10000/7000 : - 5
General
Weight UPS kg : 24.5
Dimensions UPS (h
xwxd) : 130x410x660mm
Weight battery pack kg : 67
Dimensions battery pack : 130x410x660mm
Enclosure / protection : steel-plastic / IP20
Environment
Safety : EN 62040-1
Electromagnetic compatibility : EN 62040-2 (2006)
Ambient temperature : 0 to +40ºC
Audible noise at 1 meter : < 55 dB(A), load and temperature dependent
Max. relative humidity : 90% (non-condensing)
Colour : Black - RAL 9005
modifications reserved 25 User manual GT Series 6 - 10 kVA UPS 1.0 (GB)
www.upsdirect.com
08456 445 002

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the GE Digital Energy GT6000 and is the answer not in the manual?

GE Digital Energy GT6000 Specifications

General IconGeneral
BrandGE
ModelDigital Energy GT6000
CategoryUPS
LanguageEnglish

Related product manuals