Kilsen KFP-CF Series Operation Manual 11
Basic operation
Basic operation includes those tasks that can be performed when the control panel is
in access level 1, the default access level.
Basic operation in access level 1 lets you:
Acknowledge a system event and silence the internal buzzer
Cancel an active sounder delay
Cancel an active fire routing delay
Perform a control panel LED and internal buzzer test
No other system controls are available at access level 1.
Acknowledging a system event and silencing the internal buzzer
To acknowledge a system event and silence the internal buzzer, press the Panel
Silence button.
A steady Panel Silence LED indicates that the internal buzzer was silenced and that all
current events were acknowledged.
Cancelling an active sounder delay
If a sounder delay is enabled and active, press the Sounder Start/Stop button to
cancel the delay and activate sounders immediately.
A sounder delay is indicated as follows:
A steady Sounder Delay LED indicates that a delay is enabled.
A flashing Sounder Start/Stop LED during a fire alarm indicates that the
configured delay is active (sounders are activated when the configured delay
elapses or when the delay is cancelled).
A fire alarm activated by a manual call point overrides any configured delay and
activates sounders immediately.
Cancelling an active fire routing delay
If a fire routing delay is enabled and active, press the Fire Routing Start button to
cancel the delay and activate fire routing immediately.
A fire routing delay is indicated as follows:
A steady Fire Routing Delay LED indicates that a delay is enabled.
A flashing Fire Routing Start LED during a fire alarm indicates that the configured
delay is active (fire routing is activated when the configured delay elapses or
when the delay is cancelled).
A fire alarm activated by a manual call point overrides any configured delay and
activates fire routing immediately.