Installation Guide LP33 Series 20 & 30 UL S2
4.2 DELIVERY
When delivered, check carefully the package integrity and the physical conditions of the UPS
equipment.
In case of any damage sustained during transport, immediately inform the carrier and contact your
local Service Center.
A detailed report of the damage is necessary for any insurance claim.
NOTE !
A damaged UPS must never be installed or connected to utility or battery!
4.3 STORAGE
The equipment is carefully packed for transport and storage
so that it is in a perfect condition when eventually installed.
Never leave a UPS outside the building and do not store the
UPS one on top of the other.
It is recommended to store the UPS in its original package in a
dry, dust free room and far away from chemical
substances, with temperature not exceeding -13°F to 131°F
(-25°C to 55°C).
4.3.1 Storage of the UPS
Some important functions of the UPS, such as the customized functions, are defined by parameters
stored in a RAM memory.
The RAM is supplied by a small backup battery located on the Control Unit board.
If the storage time of the UPS exceeds 1 year, these functions should be verified by an authorized
Service Center before putting the UPS into operation.
NOTE !
In case of storage of the UPS pay attention to:
4.3.2 Storage of the battery
In case of extended storage, when the delivery includes maintenance free batteries, keep in mind that
they are subject to auto-discharging process
To avoid permanent damages to the battery, you must observe the following instructions:
The storage time without charging the battery depends on the ambient temperature of the storage area.
The optimal ambient temperature for the batteries is 68°F (20°C).
For storage temperature higher than 68°F (20°C), the storage time will decrease.
Each additional 18°F (10°C) over the nominal temperature of 68°F (20°C) will decrease the storage
time, without freshening charge, by half.
In case of a maintenance free battery, the storage time without charging the battery is
approximately:
6 months with storage temperature 68°F (20°C)
3 months with storage temperature 86°F (30°C)
2 months with storage temperature 95°F (35°C)
NOTE !
In case of battery storage pay attention to:
FRAGILE
SENSITIVE
TO DAMPNESS
TO HEAT
SENSITIVE
TO FROST
SENSITIVE
FRAGILE
SENSITIVE
TO DAMPNESS
TO HEAT
SENSITIVE
TO FROST