6.5 COMMANDS
The COMMANDS mode is entered any time the “CMDS” key is pressed.
This allows the user to execute UPS operation commands.
In this mode the keys perform the following functions:
Return to HOME screen.
Scrolls forward to the next screen.
V
Scrolls forward to the next line.
Confirm the selection made.
It is possible to view any key functional description by pushing the key for more than 3 seconds.
`Home\ Commands
COMMANDS
LAMP TEST
INVERTER ON
INVERTER OFF
BOOSTER ON (Service)
V
Commands screen 1
LAMP TEST
Signaling LEDs test and buzzer test (all LED should be lit and
blinking and the acoustical alarm should be activated).
INVERTER ON
Command to switch the inverter.
INVERTER OFF
Command to shutdown the inverter.
BOOSTER ON (Service)
Service only allowed.
`Home\ Commands
COMMANDS
RESET TOTAL OFF
REQUEST TOTAL OFF
V
Commands screen 2
RESET TOTAL OFF
Restore of the command “Load Off”.
REQUEST TOTAL OFF
Command “Load Off”.
Screen sequence to execute the command “Load Off”:
`Home\ Commands
`Home\ Commands
COMMANDS COMMANDS
RESET TOTAL OFF
RESET TOTAL OFF
REQUEST TOTAL OFF
CANCEL TOTAL OFF
EXECUTE TOTAL OFF
V
V
As the command procedure
of “Load Off” is finished the
“REQUEST TOTAL OFF”
screen appears again.