7.2.2 Complete shut-down of the TLE Series 160 - 500 as frequency converter
NOTE !
Follow this procedure only in case the UPS system and the Load must be
completely powered-down.
Initial status:
Load supplied from Inverter.
1. Perform the command System shutdown.
Perform the command System shutdown” through the
screen: Commands 1 / System shutdown / Shutdown
Load is disconnected from UPS.
Rectifier and Inverter are shut-down and all contactors are
opened.
LED 1 (Rectifier) and LED 2 (Inverter) are OFF.
LED ALARM is lit.
2. Open “Q1 - UPS Output switch” (Pos. O).
3. Disconnect the Battery from the UPS by opening, if present, the “CB3 External Battery
switch” (option) and then the External Battery Protections.
NOTE !
Before performing the next procedure (4) wait 5
minutes for DC-Link Capacitors discharge.
Use the MEASURES/Rectifier screen to ensure
that the DC-link1 and DC-link 2 voltage has
reached 10Vdc.
Press “MUTE” key to reset Acoustical Alarm.
LED ALARM remains lit.
4. Disconnect the Utility from the input distribution.
END OF PROCEDURE
DANGER !
It will take 5 minutes for the DC capacitors to discharge.
Open only the front door, do not open any other part of the UPS.