Note: Nominal capacities are based on the follow conditions.
Mode
Indoor
Outdoor
Cooling
DB:27(80.6)
WB:19(66.2)
DB:35(95)
WB:24(75.2)
Heating
DB:20(68)
WB:--(--)
DB:7(44.6)
WB:6(42.8)
Piping
Length
18K-48K
5m
60K
7.5m
The air volume is measured at the relevant standard external static pressure.
Noise is tested in the semianechoic room, so it should be slightly higher in the actual operation due
to environmental change.
3.2 Operation Range
Mode
Range of Outdoor Temperature
Cooling
-15-43
Heating
-10-24
3.3 Electrical Data
3.3.1 Outdoor unit
Table 1-4-1 Electrical Data of Outdoor Unit
Model
Compressor
Fan Motor
Fuse/Breaker
Capacity
Min.
Power
Supply
Cord
Power
Supply
Qty.
RLA
FLA
V/Ph/Hz
A
A
A
mm
2
GUHN18NK3HO
220-240,1,50
1
8.4
<1
5/13
2.5
GUHN24NK3HO
220-240,1,50
1
11.3
<1
5/20
4.0
GUHN30NK3HO
220-240,1,50
1
12.7
<1
5/20
4.0
GUHN36NM3HO
380-415,3,50
1
6.9
<1
5/13
1.5
GUHN42NM3HO
380-415,3,50
1
7.2
<1
5/13
2.5
GUHN48NM3HO
380-415,3,50
1
8.7
<1
5/16
2.5
GUHN60NM3HO
380-415,3,50
1
9.3
<1
5/16
2.5