37
6.5 Function Introduction
1
Basic Function
1.1 Cooling mode
1.1.1 Coolin
gcondition and process
a.
When Tindoor amb. Tpreset+1 2 , the unit operates in cooling mode.Meanwhile, compressor and
outdoor
fan operate and indoor fa
noperates at set fan speed.
b.
When Tindoor amb. Tpreset-1 2 , compressorand outdoor fanstop operation, while indoor fan operates at
set fan speed.
c. When
Tpreset-1 2 <Tindoor amb.<Tpreset+1 2 ,the unit keeps original operation status.
1.1.2 In this mode
,the settemperature rangeis 16 ~30 61 ~86
1.2 Dry Mode
Dr
y Conditions and Process
a. When Tamb.
Tpreset+2 (4 ), the unit will operate in Cool mode, and thefan will run at low speed.
b. When Tpreset-2
(4 ) Tamb. Tpreset+2 (4 ), the unit will operate in Drymode. In that case, the indoor fan will operate
at low speed. The compressor and the outdoor fan will stop for 6 min an
doperate for 4min circularly.
c. When
Tamb. Tpreset-4 (2 ), the compressor will stop working andthe fan will operate at low speed.
Under this mode, the setting temperature range is 16~30
61~86
1.3 Heating mode
1.4.1 When Tindoor amb.
Tpreset+1 , the unit will operateat heating mode.Meanwhile, 4-way valve and compressor will
operate. Fan will operate at cold air prevention condition;
1.4.2 When Tindoor amb.
Tpreset +3 6 , compressor will stop operation while 4-way valve will be energized.Fan will
operate at blowing residualheat mode.
1.4.3 When Tpreset + 1
Tindoor amb Tpreset+3 the unit will keep itsprevious operation status;
1.4.4 Under this mode, the temperature setting range is 16-30
(61-86 ).
1.4 Fanmode
a. In this mode, compressor and electricheating pipewill stop operation and fanwill operate at setspeed.
b. In this mode, the set temperature range is 16
~30 61 ~86 .
1.6. Auto Mode
Working conditions and process
a. When Tamb.
26 (79 ), the unit will operate in Cool mode. Tpreset=25 77
b. When Tamb. 22 (72 ), the heat pump unit will operate at heating mode and thecooling only unit will operate at fan mode;
Tpreset=20
68 ;
When 22
(72 ) Tamb. 26 (79 ) , the unit will maintain its previous running state. When the unit enters into auto mode
for the first time, it will operate at fan mode.