23
Air to Water Heat Pump
Service Manual- Versati II Series
CONTROL
Full Name Displayed Name Range Default
Set Mode Mode Cool/Heat Heat
Period 1 running time Period 1 00:00-23:59 08:30
Water out temperature for cooling /
Room temperature for cooling /
Water out temperature for heating /
Room temperature for heating
WT-heat 1/
RT-heat 1/
WT-cool 1/
RT-cool 1
Refer to the temperature
setting range of
“Weekly Timer”.
35
/95
Period 1 running time Period 2 00:00-23:59 17:30
Water out temperature for cooling /
Room temperature for cooling /
Water out temperature for heating /
Room temperature for heating
WT-heat 2/
RT-heat 2/
WT-cool 2/
RT-cool 2
Refer to the temperature
setting range of
“Weekly Timer”.
35
/95
3�3�2�15 Floor Debug
1) At the homepage, by pressing the Function key access to the FUNCTION page, and then locate where
Floor debug” is, after that, press OK key to go to the FLOOR DEBUG setting page.
2) At the FLOOR DEBUG setting page, by the Left/Right key select the desired parameter and then by
the Up/Down key configure it. The configurable parameters include “Segments”, “Period 1 temp”, “ΔT of
segment”, and “Segment time”, as listed in the following table..
No� Full Name Displayed Name Range Default Accuracy
1 Segments for oor debug Segments 1~10 1 1
2 First temperature for oor debug Period 1 temp
25~35
/
77~95
25
/77
1
/1
3
Segment temperature
difference for oor debug
ΔT of segment 0~72H 0 12H
4 Segments duration for oor debug Segment time
2~10
/
36~50
5
/41
1
/1
3) After the above setting is nished, by pressing the function key no. 2 activate this function and a dialog
box will pop up, reminding “Start the Floor Debug Mode now?”. If so, press the “OK” key. Once “Floor debug
has been activated, by pressing the function key no. 2, a dialog box also will pop up, reminding “Stop the Floor
Debug Mode now?” If so, press the OK key; if not, press “Cancel” to go on.
[Notes]
This function can be activated only when the unit is OFF. When it is intended to activate this function
with the unit being ON, a dialog box will pop up, warning “Please turn off the system rst!”.
When this function has been activated, it is unable to turn on or off the unit. In this case, when pressing
the ON/OFF key, a dialog will pop up, warning “Please disable the Floor Debug Mode!”.
When this function has been set successfully, “Timer week”, “Clock timer” and “Temp timer” will be
deactivated.
“When “Floor debug” mode has been activated, “Emergen�mode”, “Sanitize”, “Holiday mode” is not

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Gree Versati II Series and is the answer not in the manual?

Gree Versati II Series Specifications

General IconGeneral
BrandGree
ModelVersati II Series
CategoryHeat Pump
LanguageEnglish

Related product manuals