62
Air to Water Heat Pump
Service Manual- Versati II Series
MAINTENANCE
F3
Refrigerant gas line temperature
sensor error
The plug on temperature sensor is
not correctly connected to the socket on
mainboard.
The resistance of temperature sensor
is not correct.
It will be automatically cleared after the
failure is removed.
dF
other thermal outlet temperature
sensor error
The plug on temperature sensor is
not correctly connected to the socket on
mainboard.
The resistance of temperature sensor
is not correct.
It will be automatically cleared after the
failure is removed.
F0 Room temperature sensor error
The plug on temperature sensor is
not correctly connected to the socket on
mainboard.
The resistance of temperature sensor
is not correct.
It will be automatically cleared after the
failure is removed.
Ec Water ow switch protection
The switch is damaged.
The wire of the switch is loose.
The position of the switch is wrong
It will be cleared after the unit is
energized again.
E2 Indoor anti-frozen protetion
The resistance of temperature sensor
is not correct.
The electric expansion valve can not
work normally.
It will be cleared once malfunction is
removed or it will be shown all the time;
but it will be cleared immediately when
switching operation mode.
No display
Sanitary water tank High-temp
protection
The resistance of temperature sensor
is not correct.
The plug on temperature sensor is
not correctly connected to the socket on
mainboard.
Mainboard of outdoor unit is damaged.
Press ON/OFF key to clear
Ed
outlet temperature High-temp
protection (This error code will not
displayed on wired controller but
only on mainboard of outdoor unit)
The resistance of temperature sensor
is not correct.
The plug on temperature sensor is
not correctly connected to the socket on
mainboard.
Mainboard of outdoor unit is damaged.
If the malfunction is removed, the code
will be automatically cleared.
No display solar outlet High-temp protection
The resistance of temperature sensor
is not correct.
The plug on temperature sensor is
not correctly connected to the socket on
mainboard.
Mainboard of outdoor unit is damaged.
Press ON/OFF key to clear
EH
Welding protection of the auxiliary
heater 1
The AC contactor is damaged.
De-energize the unit and then, energize it
again. If the malfunction is removed, the
code will be cleared.
EH
Welding protection of the auxiliary
heater 2
The AC contactor is damaged.
De-energize the unit and then, energize it
again. If the malfunction is removed, the
code will be cleared.
EH
Welding protection of the water tank
heater
The AC contactor is damaged.
De-energize the unit and then, energize it
again. If the malfunction is removed, the
code will be cleared.
dU Pull-out of the gate-controller
the gate-controller is pull out
It will be cleared after the gate-controller
is rewire

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Gree Versati II Series and is the answer not in the manual?

Gree Versati II Series Specifications

General IconGeneral
BrandGree
ModelVersati II Series
CategoryHeat Pump
LanguageEnglish

Related product manuals