CONNECT SERIES SERVICE MANUAL
9
ENGLISH
Controls
Forced Defrost Control
Press and hold the SW1 button for about 5 seconds to enter the fi
rst menu level. The outdoor unit main
board display will flash. Short-press the SW1 button to switch the function to “06”. Short-press SW2 or SW3
to change the selection within function “06” to “ON”, followed by a short-press on SW1 to save. The menu
will time out if no function is performed within 10 seconds.
Refrigerant Recovery Control
Press and hold the SW1 button for about 5 seconds to enter the first menu level. The outdoor unit main
board display will flash. Short-press the SW1 button to switch the function to “08”. Short-press SW2 or SW3
to change the selection within function “08” to “ON”, followed by a short-press on SW1 to save. The menu
will time out if no function is performed within 10 seconds.
Forced Operation Control
Press and hold the SW1 button for about 5 seconds to enter the first menu level. The outdoor unit main
board display will flash. Short-press the SW1 button to switch the function to “09”. Short-press SW2 or SW3
to change the selection within function “09” to “ON”, followed by a short-press on SW1 to save. The menu
will time out if no function is performed within 10 seconds.
Press and hold SW1 for about 5 seconds to enter the first menu level. The outdoor unit main board display will flash.
Short-press the SW1 button to switch the function to "11". Short-press SW2 or SW3 to change the selection to:
00 - Pressure
01 - Frequency
02 - Exhaust temperature
08 - Fan speed
Short-press SW1 to save. The data will be displayed on the LED.
Thermostat Functions
Please refer to your thermostat user guide for information on your thermostat functions.