CONNECT SERIES SERVICE MANUAL
55
ENGLISH
Maintenance
Model: AUH2436ZGDA
Outdoor Coil Removal
Note: Make sure all refrigerant has been recovered and power is isolated before removing the outdoor coil.
Step Picture Work instruction
1. Remove the panels.
Remove the upper, lower and front
panels.
Fan and Motor Removal
Note: Be sure to isolate power before removing the fan.
Step Picture Work instruction
5. Install the fan.
Install the fan in place. Put on the
gasket and use a wrench to secure the
screw nut.
Note: After installing the fan, turn
the fan by hand to see if it can run
normally. If not, please check for the
reason.
6. Install the grill.
After replacing the motor, use a
screwdriver to tighten up the screw
bolt that secures the motor. Arrange
the wires according to the wiring
diagram.