EasyManuals Logo
Home>Hayward>Water Pump>Max-Flo XL

Hayward Max-Flo XL User Manual

Hayward Max-Flo XL
20 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #8 background imageLoading...
Page #8 background image
USE ONLY HAYWARD GENUINE REPLACEMENT PARTS
Page 8 of 20 Max-Flo XL Pump IS2300 Rev-A1
3.5. Electrical
WARNING All electrical wiring MUST conform to local codes, regulations, and the National Electric Code
(NEC).
WARNING Ground and bond pump before connecting to electrical power supply. Failure to ground and
bond pump can cause serious or fatal electrical shock hazard. Do NOT ground to a gas supply line. To avoid
dangerous or fatal electrical shock, turn OFF power to pump before working on electrical connections. Fire Hazard -
match supply voltage to pump nameplate voltage. Insure that the electrical supply available agrees with the pump’s
voltage, phase, and cycle, and that the wire size is adequate for the amps rating and distance from the power
source. Use copper conductors only.
3.6. Electrical Specs
Use copper conductors only. For indoor & outdoor use.
PUMP MODEL
TOTAL HP
RATED HP
VOLTAGE
AMPS
SP23
05X7
0.95
0.75
115 / 208
-
230
10.0 / 6.0
-
5.0
SP23
05X7EE
0.95
0.75
115 / 208
-
230
9.2 / 4.7
-
4.6
SP2305X7EESP
0.95
0.75
1
15 / 208
-
230
9.2 / 4.7
-
4.6
SP23
07X10
1.25
1.00
115 / 208
-
230
13.3 / 6.9
-
6.8
SP23
07X102
1.25 / 0.20
1.00 / 0.16
230
SP23
10X15
1.65
1.50
115 / 208
-
230
16.5 / 9.2
-
8.5
SP23
10X152
1.65 / 0.27
1.50 / 0.25
230
7.7 / 2.8
SP23
15X20
2.10
2.00
115 / 20
8
-
230
17.4 / 10.6
-
8.8
SP23
15X202
2.20 / 0.36
2.00 / 0.33
230
10.0 / 3.0
3.7. Voltage
Voltage at pump MUST NOT be more than 10% above or below nameplate rated voltage, or components may
overheat, causing overload tripping and reduced component life. If voltage is less than 90% or more than 110% of
rated voltage when pump is running at full load, consult the power company.
3.8. Grounding and Bonding
1. Install, ground, bond, and wire pump in accordance with local or national electrical code requirements.
2. Permanently ground pump. Use green ground terminal provided under access plate; use size and type wire
required by code. Connect ground terminal to electrical service ground.
3. Bond pump to pool structure. Bonding will connect all metal parts within and around the pool with a continuous
wire. Bonding reduces the risk of a current passing between bonded metal objects, which could potentially
cause electrical shock if grounded or shorted. Reference NEC codes for all wiring standards including, but not
limited to, grounding, bonding and general wiring procedures.
4. Use a solid copper conductor, size 8 or larger. Run wire from external bonding lug to reinforcing rod or mesh.
Connect a No. 8 AWG (8.4 mm
2
) [No. 6 AWG (13.3 mm
2
) for Canada] solid copper bonding wire to the pressure
wire connector provided on the motor housing and to all metal parts of swimming pool, spa, or hot tub, and to
all electrical equipment, metal piping (except gas piping), and conduit within 5 ft. (1.5 m) of inside walls of
swimming pool, spa, or hot tub.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Hayward Max-Flo XL and is the answer not in the manual?

Hayward Max-Flo XL Specifications

General IconGeneral
BrandHayward
ModelMax-Flo XL
CategoryWater Pump
LanguageEnglish

Related product manuals