3.5 Product Data
General
Total program and data memory
for all application programs
5 MB less 64 kBytes for CRCs
Response time
6 ms
Ethernet interfaces 4 x RJ-45, 10/100BaseT (at 100 Mbit/s)
with integrated switch
Fieldbus Interfaces 2 x 9-pole D-sub
FB1 and FB2 with fieldbus submodule pluggable
Operating Voltage
24 VDC, -15 %...+20 %, r
PP
15 %,
provided by a power supply unit with safe isolation
in accordance with IEC 61131-2 requirements.
Operating data
3.3 VDC / 1.5 A
5 VDC / 0.1 A
Buffer for date/time Gold capacitor
Ambient temperature 0 °C...+60 °C
Storage temperature -40 °C...+85 °C
Space requirement 6 RU, 4 HP
Weight 280 g
Table 12: Product Data
3.6 Certified HIMatrix F60 CPU 03
HIMatrix F60 CPU 03
CE EMC
TÜV IEC 61508 1-7:2010 up to SIL 3
IEC 61511:2004
EN ISO 13849-1:2008
IEC 62061:2005
EN 50156-1:2004
EN 298:2003
EN 230:2005
PROFIBUS Nutzerorganisation
(PNO)
Test Specification for PROFIBUS DP Slave,
Version 3.0 November 2005
Table 13: Certificates
Further safety standards and application standards are specified in the certificate. The
certificate and the EC Type-Examination Certificate are available on the HIMA website at
www.hima.com.

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the HIMA HIMatrix F60 CPU 03 and is the answer not in the manual?

HIMA HIMatrix F60 CPU 03 Specifications

General IconGeneral
BrandHIMA
ModelHIMatrix F60 CPU 03
CategoryController
LanguageEnglish

Related product manuals